KZ Circular non-return flap valve
Description
A circular non-return flap valve with a spring mechanism, against air backflow.
Intended Use
This type of system element prevents warm air from escaping/migrating or cold air getting inside with the loss of the compression ratio, for example, when the duct fans are off.
The flap may be mounted both on the suction side and on the pressure side, in any position. Operating temperature: from -20°C to +90 °C.
Design
Due to the appropriately sized springs, the leaves of the damper open at relatively low overpressure, shortly after the fan has turned on. When installing in a vertical system, mount the flap according to the flow direction marked with an arrow on the non-return flap housing.
When installing in a horizontal system, keep in mind that the damper axle of the non-return flap must be oriented vertically. This position ensures the uniform arrangement of the non-return flap planes during operation.
The device holds hygiene certificate no. HK/1514/01/2012.